Chiller
Daily
- Inspect all equipment to be operating and safety systems are in place.
- Inspect set points.
- Inspect control and alarm panels.
- Inspect water supply, return and flow readings.
- Inspect abnormal noises and vibration (whilst adhering to safety requirements).
- Compressor oil level (technology depending) and oil leakage.
Monthly
- Inspect and clean evaporator and condenser.
- Inspect motors and pumps (e.g. noise, vibration, power consumption).
- Inspect water quality.
- Inspect insulation.
- Inspect pipes, valves, connections (e.g. leaks).
- Inspect control operation (e.g. hot gas bypass, liquid injection).
- Compressor oil level (technology depending).
- Measure power consumption in each component (e.g. compressors, fan motors).
Annually
- Inspect condenser tubes (e.g. Eddy current test, cleaning).
- Inspect evaporator tubes (e.g. Eddy current test, cleaning).
- Inspect compressor (e.g. seals, oil, heater).
- Inspect electrical system (e.g. connections, wiring).
- Inspect alarm contacts.
- Inspect refrigeration (e.g. levels, quality).